Off (default) = Pmax whenever DSO isn't actively limiting — matches PF2 fail-safe. Only enable this to manually verify the turbine responds to a local setpoint change; remember to disable it afterward.
0bde
Limits & Flags
Turbine Fault
A real Vestas fault (Statecode 4/5, or a non-zero error number — see the Turbine Summary page) stays latched until something sends 'N' (Ack Error) — 'O' (Run) alone does not clear it. PF2 retries this automatically while resuming from a below-minimum-power Pause (see Turbine Paused card, PF2/CCI page); use this button for any other stuck fault.
EEPROM Event Log
0bca
#
Date / Time
Event
Source
Severity
Value
Loading...
Serial Debug Console
Click Refresh to load serial log...
Site / Turbine Identification
Set once during commissioning (ProvisionDevice.ps1) — not editable here. Display-only: shown in the page title/header, has no effect on the RCS protocol.
Turbine Name
---
Client Name
---
Serial Number
---
CCI Model
---
Hardware ID
---
0bbc
Provisioned
---
Admin Password
Gates Local Override and EEPROM Event Log clearing on this unit. Requires the current password — if it's lost, use Remote Password Recovery below instead of the fields here.
Forgot the password and no one on site knows it? Remote recovery works over the network — no USB access needed. It shows a challenge code; call/message Orbital Italia support with it, and they'll give back a response code that resets the password to the factory default.
Diagnostics
FW Version
---
Uptime
---
Status Word
0x0000
Alarm Word
0x0000
0bee
Free Heap
---
Largest Free Block
---
RCS Diagnostics
Quality Score
---
TX Frames
---
RX Frames
---
Timeouts
---
CRC Errors
---
Unknown Frames
---
Avg Response Time
---
Max Response Time
---
RTC Time Settings
0bfb
Loading...
Device Control
Restart the PF2 controller. All active connections will be dropped briefly.
WiFi Configuration
Ethernet Configuration
0b41
CCI / Modbus Interface
Max time without register 40008 changing before the DSO channel is declared down (see PF2-interface.md). Applies immediately, no restart needed.
Firmware Update (OTA)
Uploading...
OTA Instructions
1. Build firmware in PlatformIO
0a02
2. Find .pio/build/<env>/firmware.bin
3. Select the .bin file above
4. Click Upload & Flash
5. Device will reboot automatically
Communication Diagnostics
Start with Auto Detect when commissioning a turbine link. Use Communication Setup only for manual overrides.